Model: P4RL
Category: Notification Appliances, Sounder Strobes
Brand: System Sensor
Dealer pricing
General
L-Series standard horns, strobes, and horn strobes shall mount to a standard 2 x 4 x 17/8-inch back box, 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double-gang back box. L-Series compact products shall mount to a single-gang 2 × 4 × 17/8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products for all standard models and a separate universal mounting plate shall be used for mounting wall compact models. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series products, when used with the SyncCircuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the SyncCircuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 30, 75, 95, 110, 135, and 185.
Strobe
The strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non-coded power supply.
Alarm Type | Audible, Visual, Audible, Visual |
Application/Usage | Fire Alarm, Indoor, Indoor, Fire Alarm |
Brand Name | System Sensor |
Category Type | Sounder Strobes |
Color | Clear Lens, Red Housing, Red Housing, Clear Lens |
Compatibility | : |
Connectivity Technology | Wired |
Depth | 2.5" |
Durability | Tamper Resistant |
Features | Tamper Resistant |
Form Factor | Wall Mountable |
Height | 4.7" |
Input Voltage | 33 V |
Length | 5.6" |
Model | P4RL |
Power Source | DC |
Product Functions | Alarm |
Product Series | L |
Product Type | Horn/Strobe |
Sound Emission | 88 dB(A) |
Vendor Name | System Sensor |
Width | 4.7", 5.6", 2.5" |